| Sample | about 120 recorded fault events; 50 feeders, 13 utilities, about 18 months | 64,382 fault sequences; 676 feeders, 22 utilities, 2,244 monitor-years |
| Smallest faults seen | very few records below 800 A (trigger levels set high to avoid load) | 50% of sequences peak below 800 A |
| Fault current | line-to-ground average 2,095 A; largest 6,100 A | average 1,080 A, median 800 A (the largest in each sequence); 1,720 A average above 800 A |
| Fault current duration | line-to-ground average 8.35 cycles per event, every opening counted; longest event 73 cycles | median 3.5 cycles (every shot in a sequence); average 19.7, pulled up by a long tail: 10% of sequences run past 49 cycles, 6% past 73 (the 1983 study’s longest) |
| Single phase to ground | 79% of the faults utilities reported | 83% of sequences by the configuration held longest (as EL-3085 typed its events); 79% at the widest configuration each reached |
| One fault per event | about 80% of recorded events (126) | 77% of sequences; 1.47 faults per sequence on average |
| One breaker opening was enough | about 85% of events where the breaker operated (66) | 78% of 8,619 reclose attempts where the substation breaker opened |
| A fuse cleared the permanent fault | 88% of 237 faults utilities reported (they had estimated 59%) | 55% to 64% of sequences that ended with load lost (likely fuse blow; with "fuse unconfirmed") |