What faults really do
DFA records every fault at the substation, on circuits utilities run every day. This site publishes what that fleet sees, rebuilt from the live data.
64,382fault sequences recorded
676US feeders
22utilities
2,245monitor-years of recordings
Studies
Measured, not assumed
Fault study
Faulty Assumptions
Textbooks say about 80% of faults are temporary. We followed 64,382 fault sequences to the customer to find out.
Read the study → LibraryReclosing library
1,673 papers, patents, reports and books on automatic reclosing, from 1884 to 2026, in 12 languages.
Browse the library →
Coming soon
Reliability study
Feeder reliability
How reliable are feeders across Texas and Illinois, measured circuit by circuit?
How we measure
One monitor per feeder. Existing CTs and PTs.
Each DFA unit sits in the substation and watches an entire feeder through the instrument transformers already there. It turns every fault into an answer: what happened, which device acted, and who lost power.